Page 4 - FlowCon SH Brochure

FlowCon International can accept no responsibility for possible errors in any printed material. All rights reserved. June 2010 001
D e n m a r k
D u b a
i
U S A
B r a s i l
S i n g a p o r e
SH1 DN15/20/25 SH2 DN25/32/40
SH3 DN50/65/80
SH4 DN80/100
SH5 DN125/150
Pressure Differential
(
kPaD)
33-300
33-300
35-400 35-400 80-400 35-400
60-400
35-400 60-400
(
psid)
4.8-44
4.8-44
5.1-58 5.1-58 11.6-58 5.1-58
8.7-58
5.1-58 8.7-58
Flow Rate
(
l/sec)
0.075-0.70
0.11-1.95 1.48-4.16 2.57-7.15 3.55-9.88 3.49-9.38 4.73-14.2 3.68-20.2 6.48-23.3 7.10-29.5
(
GPM)
1.20-11.1
1.70-30.9 23.4-66.0 40.7-113 56.3-157 55.4-149 75.0-225 58.3-320 103-369 113-468
Static Pressure
(
kPa)
2500
4000
(
psi)
360
580
Temperature Rating
(
media / ambient)
(
ºC)
-20
to +120 / -10 to +54
(
ºF)
-4
to +248 / +14 to +131
Pressure Drop Data
NOTE: For pump head calculations, add the minimum pressure differential for the index circuit to the other components pressure
losses (i.e. valves, coil, etc.)
Valve
(
Kv-value) (m³/hr)
4.2
11.6
24.0
39.5
58.3
89.0
132,3
(
Cv-value) (GPM)
4.9
13.5
27.8
45.8
67.6
103.2
153.5
Technical Data
For further information please see FlowCon tech note. For latest updates please see
.
Flow Verification
Optional pressure/temperature test plugs are avail-
able for verifying the differential pressure across
each FlowCon SH valve. They are fitted into 1/4’’
NPT female threaded ports. With the p/t plugs
fitted, a pressure differential reading across the valve
can be taken.
Flow Rate Setting
For adjusting the flow rate of the FlowCon SH
valves use the special designed key (FlowCon part
no. ACC0001). As an example, a micrometer setting
at 2.4 corresponds to a flow rate of 0.29 l/sec for the
valve in size 15/20/25.